wft dft · Engineering Calculator

WFT to DFT Conversion Calculator for Epoxy Coating at 250 Microns DFT

Formula

DFT = (WFT × VS) / 100, and WFT = (DFT × 100) / VS

Governing Standard

SSPC-PA2 and ISO 19840 — Coating Thickness Measurement

Required Inputs

  • Wet Film Thickness (WFT) in microns (if known)
  • Dry Film Thickness (DFT) in microns (if known)
  • Volume Solids (VS) in %
  • Area to be coated in m²

Output

Missing WFT or DFT, Theoretical Coverage in m²/L, and Paint Consumption in Liters

Notes

For an epoxy coating with 65% volume solids targeting 250 microns DFT: WFT = (250 × 100) / 65 = 385 microns. Theoretical coverage = (10 × 65) / 250 = 2.6 m²/L. For 100 m² area: consumption = 100 / 2.6 = 38.5 liters. Always add 10-20% loss factor for practical consumption.